Error 212 on a Milltronics BW500 means the measured belt speed has passed roughly twice the design speed, and error 213 means the calculated rate has passed roughly three times the design rate. A real over speed is rare. The code usually means the setup in the integrator no longer matches the conveyor, classically after a speed sensor swap.
This guide covers what the two codes compare, the timed belt check that settles it, and what your tonnes are doing meanwhile. For the rest of the BW500’s codes, see our BW500 fault codes and calibration guide. For bookings and parts, see Siemens Milltronics belt scale and BW500 servicing. We’re an independent service company, not a Siemens dealer or agent.
What do errors 212 and 213 actually measure?
Both compare a live figure with one entered at commissioning: measured speed against design speed, and calculated rate against design rate. Those two figures also set the design load the unit treats as full scale, which its analogue output and rate alarms are scaled from.
Either code can drive a diagnostic alarm relay, so a 212 sometimes reaches the control room as a general fault before anyone has read the display.
Why is a real over speed almost never the cause?
A drive running at twice its design speed is something you’d hear from the walkway. Usually the belt is doing what it always did, and the integrator’s idea of it has changed. The usual causes:
- A wrong speed constant. The unit turns pulses into speed with a constant in pulses per metre of belt travel, set from the sensor’s pulses per revolution and the circumference of the pulley or wheel it turns with. Change either and the right constant changes. The classic is a “like-for-like” sensor swap that wasn’t: double the pulse count and the display reads double. Moving a sensor to another shaft or pulley does the same.
- Noise counted as pulses. Extra edges from a variable speed drive, a damaged shielded run or a shield earthed at both ends read as belt travel that never happened.
- Slip. A sensor on a pulley or wheel that slips tells the truth about what it’s bolted to, not about the belt. Where a second speed sensor is fitted, the unit can compare two points on the conveyor and alarm when they drift apart. That’s the tidiest way to catch slip.
- No speed sensor at all. Where the speed input is simply linked out, the unit reports design speed straight back, so a speed alarm there isn’t about the belt. The contact standing in for a sensor also has to open when the conveyor stops, or the unit keeps totalising on a stopped belt.
Sensor type and polarity matter too: see our belt weigher speed sensors guide. No speed signal at all is a different job.
How do you prove whether the belt is really running that fast?
Work on or near a conveyor, or inside an electrical enclosure, needs isolation under your site’s procedures and trained, authorised people. If that’s not you, stop and call us on 1300 101 666.
Time it. Mark a measured length of belt with the conveyor stopped and isolated, then time the marks passing the weigher from a safe position well clear of the belt. Length divided by time is the real belt speed. More than about 2% off the display needs investigating, and the pattern tells you where to look:
- Timed speed agrees with the display: the unit is measuring correctly and something real has changed.
- Display is a clean multiple or fraction of the timed speed: the speed constant is wrong. The ratio is usually a tidy number that points straight at a pulse count or a pulley diameter.
- Display jumps about while the timed speed holds steady: it’s counting noise.
Example only: the constant is set for a 2-pulse sensor and someone fits a 4-pulse one. A belt running 2.5 m/s now displays 5 m/s, and every tonne reads double.
The unit also shows the incoming pulse frequency in hertz. Frequency divided by the speed constant is the speed it’s reporting, so the two figures together separate pulses genuinely arriving too fast from a constant dividing them wrongly.
If the sensor itself needs replacing, our own USR speed sensor mounts on the tail drum or a trailing arm, and its multiple outputs let one sensor feed two belt weighers, or a belt weigher plus the conveyor underspeed. We’ll confirm it suits the BW500 input and set the speed constant to match.
Why does 213 fire when the speed reads correctly?
Rate is load per metre times speed, so if the speed is right the load side is doing it. Load per metre is anchored to dimensions someone typed in: the span reference is the test weight mass divided by the average idler spacing across the weigh area. Enter a spacing shorter than the real one and every kilogram per metre inflates in proportion, and the rate with it.
Example only: 60 kg of test weight over a real 1.2 m spacing is 50 kg/m. Enter 1.0 m and the unit takes it as 60 kg/m, so everything reads 20% high while the speed stays correct.
The other cause is that nothing is broken and the plant is simply run harder. Design rate is a commissioning figure, and conveyors get debottlenecked. That’s a business question rather than a fault, but it needs answering: the scale is only proven near the rate it was calibrated at. And the pulse output that feeds the plant’s own totaliser is sized around the design rate with only modest headroom, so a conveyor running well past its rating can leave the control system’s total quietly trailing the integrator’s.
What are your tonnes doing while 212 or 213 is showing?
The totaliser keeps running, and each cause leaves its own signature:
- a wrong speed constant is a clean bias: every tonne out by the same ratio, in the same direction, all day
- counted noise over-reads only while the noise is there, so totals won’t repeat. That’s the pattern in erratic totals.
- a sensor on a slipping drive pulley over-reads while it slips
- a wrong idler spacing is another proportional bias, with the speed innocent
- a plant truly above design rate may be totalising correctly, but outside the range anyone has proven.
From outside the guard, your site can work out when the code appeared and what changed that week (a sensor, drive work, a belt, a control upgrade), check the tonnes since then against the weighbridge, and look at the sensor cable for damage or a run alongside power cable.
Don’t lift the design figure to quieten the alarm before the speed is proven. That raises the trip point, changes what full scale means on the outputs, and moves the reference the next calibration is judged against. The code goes away and the tonnes stay wrong.
Need a manual for your equipment?
The speed constant, design speed and design rate behind a 212 or 213 were entered at commissioning, so no manual will tell you why yours fired. Check whether the nameplate says BW500 or BW500/L, because the two have different feature sets.
Talk to us about manuals for your equipment. Send the make, model, serial number and software version (a photo of the label is fine) and we’ll help you find the right document.
When should you call us?
Call when the code survives a check of the sensor and its wiring, when the timed speed disagrees with the display, when it followed a sensor swap or drive work, or when the plant has outgrown its design rate. That last one is a proper re-rate: new design figures, then a fresh zero, span and material test. Ring 1300 101 666, or see Siemens Milltronics belt scale service.
We supply parts for Siemens Milltronics and the other major belt weigher brands: a genuine part where it’s available, or a suitable alternative, with compatibility confirmed and the part identified on the quote.
Frequently asked questions
What does error 212 mean on a Milltronics BW500?
The measured speed has passed roughly twice the design speed. Check the speed constant against the sensor and pulley actually fitted, because a swapped or moved sensor explains most of them.
Can I raise the design rate to clear error 213?
Only once the speed and load figures are proven right, and then as a proper re-rate with a fresh zero, span and material test. Raising it just to clear the alarm moves what the outputs and the next calibration are judged against.
Will 212 or 213 stop my belt weigher totalising?
No. Both are threshold alarms and the unit keeps counting on the numbers it has. A scale can run for months with a clean-looking total that’s out by a fixed ratio.